Data Center Jakarta

 

State of Art Purpose Built Panel Room & Power House

  • All Panels Manufactured Specifically for 2 Mega (PLN) & 2 Mega (Gas) Generator
  • Transformer Distributor & Cubical Are Co-located Inside the Panel Room
  • Purpose Built Trench Ducted High Voltage Electrical Cable Routes
  • External Secure Access for Maintenance Staff & Hardware Swap outs
  • PLN Constructed Purpose Built Power House (2 Megawatt)

Superior Transformer, Cubical Transformer & UPS

  • Transformer Distributor: 2500 kVA, -400/231 V, Dyn 5, 3 Phase – Trafindo
  • Voltage Transformer Cubical Incoming: LBS IS/C410,24kV, 630A,16kA/1s – Unindo
  • UPS : APC: 200 kVa, MGE Galaxy 7000 – Schneider Redundancy (2N Paradigm)
  • Stand Alone PLN Compliant Power House
  • Legran Power Box, Ceiling Power/UTP/FO Cable Housing

Stand Alone Building: 2450 Sqm Available Data Centre

  • 350 Sqm Per/Floor x 7 Floors – 90 x 42U Perforated Racks Per Floor
  • Enclosed Perforated Rack w/- 19" 42 U, 10 A PowerProvision, 2 Ethernet 10/100 MPBS
  • Support Space to Raised Floor Ratio: 100+ %, Gross Weight: 150 +
  • Total Floor Space Can Accommodate up to 540 x 42U Perforated Racks
  • 74 Sqm ‘Meet Me Room’, Dedicated FO Ring System Throughout Jakarta CBD

Available Power

  • QDC provide AC and DC power in various configurations of amperage and voltage.
  • N+1 redundancy in power distribution, UPS systems and generator backup
  • 24 hours worth of generator fuel and contracts with multiple fuel providers
  • Industry leading availability

World Class Cooling System, Three Units Per Floor

  • Uninterruptable Cooling System: 3 X STULZ (CyberAir 2, 101.9 kW) – Germany
  • Comprehensive HVAC Air-conditioning with:
  • Precision N+1 Paradigm Up-Flow System
  • Consistent 18-22 C Temperature & 40-60% Humidity

State of The Art Integrated Fire Suppression System

  • Integrated PyroGen Piped Fire Suppression System
  • State of Art Smoke, Heat & Fog Detection System
  • Fire Suppression: FM 200 System (Gas CF3CF2FC(0)CFCF3)
  • Fire Control Panel: NFS-320 (E)
  • Smoke Detector: Photo FSP 851

QDC Telecommunications Systems

  • Brocade
  • Juniper

High Pressure Laminated Anti Static Raised Floor

  • Uniflair (30 KFP) – Japan
  • Distribution Loading: 3.1 k Sqm, Height: 50 cm (150 M/Ton/Sqm)
  • Support Space to Raised Floor Ratio: 100+ %
  • Adjustable to Rebalance with Various Rack Weights
  • Interchangeable to Align with Hot/Cold Corridors
  • Designed for Aircon Up flow Towards Hot Racks